Communications
10.2 Acyclic data exchange
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
167
Data record 160 "Control of internal fans"
The data set describes an HCS function and addresses the HCS.
Byte
Bit
Description
0
0
Control of internal fans
0: Temperature controlled internally (default)
1: All fans are switched on
1 ... 7
0
Definition is via an element of the type "Byte".
Data set 190 "System reset by user"
The data set describes an HCS function and addresses the HCS.
Byte
Description
0
"R"
1
"I"
2
"S"
3
"I"
4
"T"
5
"!"
An array with 6 entries of the type "Char" is used here.
NOTICE
The data entered must not be modified.
The data set is acknowledged before the controller performs a reset about 2 seconds later.