Communications
10.3 Transfer of diagnostic alarms to the controller
SIPLUS HCS4200 PROFINET/PROFIBUS DP
176
Operating Instructions, 07/2019, A5E35066204A/006
Error codes POM
Error code
(hex)
Description
POM4220
Lowend
POM4220
Midrange
phase
angle
control
POM4220
Flexible
POM4220
Highend
POM4320
5101
Communication error on HCS bus
✓
✓
✓
✓
5104
Channel fault:
Triac breakdown
✓
✓
✓
✓
5105
Channel fault:
•
Triac has high resistance
•
Outgoing fuse defective
✓
✓
✓
✓
5106
Channel fault:
Return fuse defective
–
–
–
✓
5107
Channel fault:
•
Defective heating element
•
External fault
✓
✓
✓
✓
5109
Switch-off threshold for internal
device temperature
✓
✓
✓
✓
510B
At least one voltage is not con-
nected
–
–
✓
✓
510C
Channel fault:
undefined
✓
✓
✓
✓
510E
Rotating field error
–
–
✓
1)
✓
510F
Phase LX1 is not connected.
✓
✓
✓
–
5110
Phase LX3 is not connected.
✓
✓
✓
–
5113
Channel fault: Partial load failure
–
–
✓
–
5114
Channel fault:
Current load too high
–
–
✓
–
5115
Phase current LX1 too high
–
–
✓
–
5116
Phase current LX3 too high
–
–
✓
–
5117
Channel fault:
Power setpoint is not reached
–
–
✓
–
5118
Channel fault:
Fault current too high
–
–
✓
–
5119
Channel fault:
Adaptive soft start cannot be
ended
–
–
✓
–
1) Rotating field error is only detected with connection type "Economy circuit"