Process and system messages, error handling
11.2 Power Output Module (POM)
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
181
Causes of errors and possible remedies
Error
code
Description
Possible causes and solutions
5104
Channel fault: Triac break-
down
"Breakdown" means the triac
is defective and conducts
continuously even without
being activated. For a 100 %
setpoint, the fault can be
neither detected nor flagged.
•
Triac is defective
⇒
Return POM
5105
Channel fault:
Fuse tripped or triac has
high resistance
•
Switch off machine, check fuse, cabling, heating ele-
ment and rectify fault, restart
•
Triac is defective => Return POM
5106
Return fuse tripped
•
Switch off machine, check return fuse, cabling, heating
element and rectify the fault, restart
5107
Channel fault:
Heating element or radiator
wire defective
•
Switch off machine, check cabling and heating element
and rectify fault, restart
•
For POM4220 Highend, connection type "phase-phase":
Check incoming fuse
•
For POM4220 Highend, connection type "2-pin switch-
ing": Check fuse
5109
Switch-off threshold for in-
ternal device temperature
Trip threshold overshot: The heating is switched off auto-
matically by the device.
Actions:
•
Check that the fan module is functioning correctly, if
installed
•
Switch off the machine, rectify the fault (e.g. cooling
malfunction), restart
510B
At least one voltage is not
connected
•
Check power supply, cabling and, if necessary, connect
the missing voltage
510E
Rotating field error
•
Check power supply, cabling and, if necessary, connect
the missing voltage
510F
Phase LX1 is not connected.
•
Check power supply, cabling and, if necessary, connect
the missing voltage
•
Configure parameter "Phase LX1 / LX3" as "not con-
nected"
5110
Phase LX3 is not connected.
5113
Channel fault: Partial load
failure
•
Switch off machine, check cabling and heating elements
and rectify fault, restart
5114
Channel fault: Current load
too high
•
Switch off machine, check cabling and heating elements
and rectify fault, restart
5115
Phase current LX1 too high
•
Switch off machine, check cabling and heating elements
and rectify fault, restart