Technical specifications
13.3 Technical Specifications CIM4210C
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
211
Article number
6BK1942-1AA00-0AA1
Interrupts/diagnostics/status information
Number of status displays
3
LED status display
LED green = ready, LED yellow = heating on/off,
LED red = error display
Isolation
Overvoltage category
III
Degree of pollution
2
EMC
EMC interference emission
Limit value in accordance with IEC 61000-6-
4:2007 + A1:2011
Electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharging, 8 kV air discharging
Field-related interference acc. to IEC 61000-4-
3
10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0
GHz), 1 V/m (2.0 ... 2.7 GHz)
Conducted interference due to burst acc. to
IEC 61000-4-4
2 kV power supply lines, 2 kV PROFINET cables
Conducted interference due to surge acc. to
IEC 61000-4-5
DC supply lines: 0.5 kV symmetric and unsym-
metric PROFINET cables: 1 kV unsymmetric
Conducted interference due to high-frequency
radiation acc. to IEC 61000-4-6
10 V (0.15 ... 80 MHz)
Degree and class of protection
IP degree of protection
IP20
Standards, approvals, certificates
Reference designation according to DIN EN
81346-2
K