Technical specifications
13.3 Technical Specifications CIM4210C
SIPLUS HCS4200 PROFINET/PROFIBUS DP
212
Operating Instructions, 07/2019, A5E35066204A/006
Article number
6BK1942-1AA00-0AA1
Ambient conditions
Ambient temperature during operation
•
min.
0 °C
•
max.
55 °C
Ambient temperature during stor-
age/transportation
•
Storage, min.
-25 °C
•
Storage, max.
70 °C
•
Transportation, min.
-25 °C
•
Transportation, max.
70 °C
Air pressure acc. to IEC 60068-2-13
•
Operation, min.
860 hPa
•
Operation, max.
1 080 hPa
•
Storage, min.
660 hPa
•
Storage, max.
1 080 hPa
Altitude during operation relating to sea level
•
Installation altitude above sea level, max.
2 000 m
Relative humidity
•
Operation at 25
℃
, max.
95 %
•
Operation at 50
℃
, max.
50 %; 95 % at 25 °C, decreasing linearly to 50 %
at 50 °C
Vibrations
•
Vibration resistance during operation acc.
to IEC 60068-2-6
10 ... 58 Hz / 0.075 mm, 58 ... 150 Hz / 1 g
•
Vibration resistance during storage acc. to
IEC 60068-2-6
5 ... 8.5 Hz / 3.5 mm, 8.5 ... 500 Hz / 1 g
Shock testing
•
Shock resistance during operation acc. to
IEC 60068-2-27
15 g / 11 ms / 3 shocks/axis
•
Shock resistance during storage acc. to
IEC 60068-2-29
25 g / 6 ms / 1 000 shocks/axis
Dimensions
Width
104 mm
Height
339 mm
Depth
296 mm
Summary of Contents for SIPLUS HCS Series
Page 1: ...SIPLUS HCS4200 PROFINET PROFIBUS DP ...
Page 2: ......