Technical specifications
13.4 Technical specifications of POM
SIPLUS HCS4200 PROFINET/PROFIBUS DP
220
Operating Instructions, 07/2019, A5E35066204A/006
Article number
6BK1942-2DA00-0AA0
6BK1942-2FA00-0AA0
Connection method
•
Design of electrical connection for
supply voltage
Connector, 3-pole with spring-loaded connection
–
Connectable conductor cross-
sections, solid
1x (0.75 ... 16 mm²)
–
Connectable conductor cross-
sections, finely stranded with
wire end processing
1x (0.75 ... 16 mm²)
–
Connectable conductor cross-
sections for AWG cables
1x (18 ... 4)
Input voltage
Design of the power supply
Power supply via rack
Power
Active power input, max.
1 W
Power electronics
Type of load
Ohmic load
Type of control of the heating elements Half-wave control, phase
control and soft start
Half-wave control
Power capacity, max.
40 kW; At 400 V AC
23 kW; At 230 V AC
•
For phase against phase with fan at
40 °C, max.
40 kW; At 400 V AC
•
For phase against phase without
fan at 40 °C, max.
12.5 kW; At 400 V AC
•
For phase against neutral with fan
at 40 °C, max.
23 kW; At 230 V AC
•
For phase against neutral without
fan at 40 °C, max.
7.3 kW; At 230 V AC
Switching capacity current per phase,
max.
50 A
Short-time withstand current (SCCR)
acc. to UL 508A
100 kA
Load connection type
Star connection with neutral conductor
(single-phase)
Yes
Open delta connection (single-phase)
Yes
No
Closed delta connection (3-phase)
No
Star connection with neutral conductor
(2-phase)
Yes; Economy circuit
No
2-pole switching
Yes; Phase – neutral con-
ductor, phase – phase
No