Technical specifications
13.4 Technical specifications of POM
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
233
Article number
6BK1943-2CA00-0AA2
6BK1943-2DA00-0AA2
Integrated Functions
Monitoring functions
•
Temperature monitoring
Yes
•
Type of temperature monitoring
NTC thermistor
Measuring functions
•
Voltage measurement
Yes
•
Current measurement
No
•
Fault current detection
No
Potential separation
Design of electrical isolation
Optocoupler and/or protective impedance between main
circuit and PELV
between the outputs
No
Isolation
Overvoltage category
III
Degree of pollution
2
EMC
EMC interference emission
Limit value in accordance with IEC 61000-6-4:2007 +
A1:2011
Electrostatic discharge acc. to IEC
61000-4-2
4 kV contact discharge / 8 kV air discharge
Field-related interference acc. to IEC
61000-4-3
10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m
(2.0 ... 2.7 GHz)
Conducted interference due to burst
acc. to IEC 61000-4-4
2 kV power supply lines, 2 kV load lines
Conducted interference due to surge
acc. to IEC 61000-4-5
on supply and load lines: 1 kV symmetric, 2 kV unsym-
metric
Conducted interference due to high-
frequency radiation acc. to IEC 61000-
4-6
10 V (0.15 ... 80 MHz)
Degree and class of protection
IP degree of protection
IP20
Standards, approvals, certificates
Reference designation according to
DIN EN 81346-2
Q