Article number
6BK1900-0BA00-0AA0
Output current
•
for signal "1" permissible range, max.
500 mA
Connection method
•
Design of electrical connection at the digital
outputs
2x 18 pole connector with spring-loaded connec-
tion
–
Connectable conductor cross-sections,
solid
1x (0.2 ... 1.5 mm²)
–
Connectable conductor cross-sections,
finely stranded with wire end pro-
cessing
1x (0.25 ... 1.5 mm²)
–
Connectable conductor cross-sections
for AWG cables
1x (24 ... 16)
•
Design of electrical connection for control
supply voltage
2x 18 pole connector with spring-loaded connec-
tion
–
Connectable conductor cross-sections
with wire end processing
1x (0.25 ... 1.5 mm²)
–
Connectable conductor cross-sections
for AWG cables
1x (24 ... 16)
Interfaces
Interfaces/bus type
system interface
Interrupts/diagnostics/status information
Number of status displays
18
LED status display
LED green = Ready, LED red = Error display, 1
LED yellow per output: LED on - H status; LED
off -L status
Potential separation
between outputs and system interface
Yes
Isolation
Overvoltage category
III
Degree of pollution
2
EMC
EMC interference emission
Limit value in accordance with IEC 61000-6-
4:2007 + A1:2011
Electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge
Field-related interference acc. to IEC 61000-4-
3
10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0
GHz), 1 V/m (2.0 ... 2.7 GHz)
Conducted interference due to burst acc. to
IEC 61000-4-4
2 kV signal lines
Conducted interference due to surge acc. to
IEC 61000-4-5
DC supply cables: 0.5 kV balanced and unbal-
anced
Conducted interference due to high-frequency
radiation acc. to IEC 61000-4-6
10 V (0.15 ... 80 MHz)
Degree and class of protection
IP degree of protection
IP20