Technical specifications
13.5 Technical specifications for I/O module
SIPLUS HCS4200 PROFINET/PROFIBUS DP
238
Operating Instructions, 07/2019, A5E35066204A/006
PM4000 U/I
Article number
6BK1900-0CA00-0AA0
General information
Product type designation
I/O4000 U/I
Installation type/mounting
Mounting type
Screw mounting to CIM
Mounting position
vertical
Type of ventilation
Forced ventilation
Supply voltage
Design of the power supply
Power supply via CIM
Power
Active power input, max.
1 W
Interfaces
Interfaces/bus type
system interface
Interrupts/diagnostics/status information
Number of status displays
2
LED status display
LED green = Ready, LED red = Error display
Integrated Functions
Measuring functions
•
Voltage measurement
Yes
•
Current measurement
Yes
Measuring inputs for voltage
–
Operational voltage at 50 Hz AC, min.
230 V
–
Operational voltage at 50 Hz AC, max. 480 V
–
Operational voltage at 60 Hz AC, min.
230 V
–
Operational voltage at 60 Hz AC, max. 480 V
–
Relative measuring accuracy voltage
0.5 %
–
Operating frequency, min.
50 Hz
–
Operating frequency, max.
60 Hz
–
Design of electrical connection at the
measuring inputs for voltage
Connector, 6-pole with spring-loaded connection
–
Connectable conductor cross-sections,
solid
1x (0.2 ... 10 mm²)
–
Connectable conductor cross-sections,
finely stranded with wire end pro-
cessing
1x (0.25 ... 6 mm²)
–
Connectable conductor cross-sections
for AWG cables
1x (24 ... 8)