Technical specifications
13.5 Technical specifications for I/O module
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
241
PM4000 Temperature
Article number
6BK1900-0AA00-0AA0
General information
Product type designation
I/O4000 Temperature
Installation type/mounting
Mounting type
Screw mounting to CIM
Mounting position
vertical
Type of ventilation
Forced ventilation
Supply voltage
Design of the power supply
Power supply via CIM
Power
Active power input, max.
1 W
Analog inputs
Number of analog inputs
•
for 2-wire system
4
•
for 4-wire system
2
Type of A/D conversion
Sigma Delta
Conversion time
150 ms
Sensor current, typ.
210 µA
Impulse voltage resistance, max.
15 V
Input for analog temperature sensor
Yes
Measuring range
•
Temperature for type J thermocouple, min. 0 °C
•
Temperature for type J thermocouple, max. 650 °C
•
Temperature for type K thermocouple, min. 0 °C
•
Temperature for type K thermocouple,
max.
440 °C
•
Temperature for type L thermocouple, min. 0 °C
•
Temperature for type L thermocouple, max. 640 °C
•
Temperature for Pt 100 according to IEC
60751, min.
0 °C
•
Temperature for Pt 100 according to IEC
60751, max.
410 °C
•
Temperature for Pt 1000 according to IEC
60751, min.
0 °C
•
Temperature for Pt 1000 according to IEC
60751, max.
850 °C
Summary of Contents for SIPLUS HCS Series