Application planning
4.4 Installation location
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
35
Unpacking and checking the delivery
1.
Unpack the device.
2.
Make sure that the package is complete.
3.
Check the device for transport damage by visual inspection.
NOTICE
Damage to the system
Damaged parts can result in damage to the system.
Only put undamaged parts into operation.
4.4
Installation location
4.4.1
General requirements for the location of use
The SIPLUS HCS4200 heating control system is designed for stationary installation in a
control cabinet. The rack forms the "outer frame" of the heating control system that you
install in the control cabinet.
Installation location requirements
WARNING
Electric shock hazard
May cause death or serious injury
In order to reliably prevent hazards for the operating personnel, the control cabinet must
satisfy the following requirements:
•
Closed cabinet
•
Grounded cabinet
•
The control cabinet and device connection box must satisfy the regulations regarding
fire-protection housing.
•
Boards and components on the reverse side of the rack must not come into contact with
cables that have only single insulation and are routed through the control cabinet.