Application planning
4.4 Installation location
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
37
Mounting position and clearance dimensions
●
The rack is mounted in the horizontal position. The Power Output Modules (POM) are
inserted vertically in the rack.
●
Maintain the minimum clearances from walls and other devices:
–
Sides 0 mm (stackable)
–
Top 100 mm, bottom 100 mm for ventilation and deaeration
Figure 4-1
Clearances for installing an HCS4200
NOTICE
Damage due to overheating
•
You must comply with all the instructions regarding the installation location and
mounting position. Otherwise the device may malfunction or incur permanent damage
as a result of overheating.
•
Ensure that the permissible ambient temperature range is not exceeded (see Section
Technical specifications (Page 205)).
Pollution degree
SIPLUS HCS4200 is designed for pollution degree 2. Pollution degree 2 is defined as follows
in the EN 50178 standard: In normal circumstances, only non-conductive pollution occurs.
However, conductivity can occur occasionally and temporarily due to condensation when the
device is not in operation.