6.2 Connecting the protective conductor
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
71
6.2
Connecting the protective conductor
WARNING
Risk of electric shock
Can cause death or serious injury
•
The protective conductor must be connected to the threaded pin indicated.
•
HSC4200: The cable cross-section for the protective conductor must be
≥
10 mm
2
.
•
HSC4300: The cable cross-section for the protective conductor must be
≥
16 mm
2
.
•
The cable lug used must have a tin-coated surface to ensure corrosion protection.
•
When connecting the protective conductor, the applicable national and local regulations
must be observed.