Communication
9.4 Diagnostics data
SIPLUS HCS3200
Operating Instructions, 07/2014, A5E31278506C/002
47
9.4
Diagnostics data
if new diagnostic data is available, this causes an OB82 call (diagnostic alarm OB). The data
can be read using system function SFC13 (DPNRM_DG).
Table 9- 3
Diagnostics data
Byte
Bit
Meaning
Description
0 ... 5
Standardized diagnostic information
-
6 ... 9
Reserved
-
10
0
= 0: Temperature OK
= 1: Temperature trip threshold reached
Refer to section Temperature moni-
1
= 0: Internal fan OK
= 1: Internal fan fault
Refer to section Temperature moni-
2
= 0: Frequency OK
= 1: Frequency fault
Refer to section Frequency monitor-
3
= 0: Line voltage OK
= 1: Line voltage outside the working
range
Refer to section Line supply voltage
monitoring (Page 41)
4
= 0: Line voltage OK
= 1: Line voltage outside the measuring
range
5 ... 7
0 (reserved)
-
11
Frequency 50 / 60 / 0 (not recognized)
Refer to section Frequency monitor-
12
Error information for power output 1
(error code 1 ... 4)
Refer to section Power output diag-
13
Error information for power output 2
(error code 1 ... 4)
14
Error information for power output 3
(error code 1 ... 4)
15
Error information for power output 4
(error code 1 ... 4)
16
Error information for power output 5
(error code 1 ... 4)
17
Error information for power output 6
(error code 1 ... 4)
18
Error information for power output 7
(error code 1 ... 4)
19
Error information for power output 8
(error code 1 ... 4)
20
Error information for power output 9
(error code 1 ... 4)