[lo-uespg-u2-gegsys-20101108, 1, en_US]
Figure 2-48
Logic diagram of the overvoltage protection for the negative sequence voltage system V
2
The overvoltage protection for the negative sequence system can also be blocked via a binary input
>59-V2
BLOCK
. The elements of the negative sequence voltage protection are automatically blocked as soon as an
asymmetrical voltage failure is detected („fuse failure monitor“, also see Section
, margin heading Rapid Measuring Voltage Failure “Fuse-Failure-Monitor”) or when tripping of the MCB for
voltage transformers has been signaled via the binary input
>FAIL:Feeder VT
(internal indication “internal
blocking”).
Overvoltage Zero Sequence System 3V
0
depicts the logic diagram of the zero sequence voltage element. The fundamental frequency is
numerically filtered from the measuring voltage so that the harmonics or transient voltage peaks remain
largely harmless.
The triple zero sequence voltage 3·V
0
is fed to the two threshold elements
59G-1-3V0PICKUP
(address
3722) and
59G-2-3V0PICKUP
(address 3724). Combined with the associated time delays
59G-1-3V0
DELAY
(address 3723) and
59G-2-3V0 DELAY
(address 3725) these elements form a two-element over-
voltage protection for the zero sequence system. Here too, the dropout ratio can be set (
59G RESET
), address
3729). Furthermore, a restraint delay can be configured which is implemented by repeated measuring
(approx. 3 periods).
The overvoltage protection for the zero sequence system can also be blocked via a binary input
>59-3V0
BLOCK
. The elements of the zero sequence voltage protection are automatically blocked as soon as an asym-
metrical voltage failure was detected (“Fuse-Failure-Monitor”, also see Section
, margin heading “Fuse-Failure-Monitor (Non-symmetrical Voltages)” or when the trip of the mcb for
voltage transformers has been signaled via the binary input
>FAIL:Feeder VT
(internal indication “internal
blocking”).
According to
the device calculates the voltage to be monitored
3·V
0
= V
A
+ V
B
+ V
C
.
Functions
2.8 Undervoltage and Overvoltage Protection (optional) 27/59
SIPROTEC 4, 7SD80, Manual
111
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...