even if the initiating signal pulse is very short. This parameter can only be set in DIGSI at Display Additional
Settings.
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2201
Direct Trip(DT)
ON
OFF
OFF
Direct Trip (DT)
2202
Trip Time DELAY
0.00 .. 30.00 sec
0.00 sec
Trip Time Delay
2203
Iph rel.Trip
1A
0.0 .. 25.0 A
0.0 A
Minimal Phase Current to
release trip
5A
0.0 .. 125.0 A
0.0 A
2204
3I0 rel.Trip
1A
0.0 .. 25.0 A
0.0 A
Minimal 3I0 Current to
release trip
5A
0.0 .. 125.0 A
0.0 A
Information List
No.
Information
Type of
Informa-
tion
Comments
4403
>BLOCK DTT
SP
>BLOCK Direct Transfer Trip option
4417
>DTT Trip ØABC
SP
>Direct Transfer Trip INPUT Phases ABC
4421
DTT OFF
OUT
Direct Transfer Trip is switched OFF
4422
DTT BLOCK
OUT
Direct Transfer Trip is BLOCKED
4435
DTT TRIP ØABC
OUT
DTT TRIP command Phases ABC
2.10.3
2.10.4
Functions
2.10 Direct Local Trip
130
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...