The effect of the signals
VT FuseFail
(no. 170) and
VT FuseFail>10s
(no. 169) on the protection func-
tion is described in the following section “Impact of the Measuring Voltage Failure”.
Additional Measuring Voltage Failure Monitoring
Failure: Voltage absent
If no measuring voltage is available after power-on of the device (e.g. because the voltage transformers are
not connected), the absence of the voltage can be detected and reported by an additional monitoring func-
tion. If the circuit-breaker auxiliary contacts are used, they should be used for monitoring as well.
shows the logic diagram of the measuring voltage failure monitoring. A failure of the measuring voltage is
detected if the following conditions are met at the same time:
•
All 3 phase-to-ground voltages are smaller than
FFM V<max (3ph)
•
At least 1 phase current is larger than
PoleOpenCurrent
or at least 1 circuit-breaker pole is closed
(settable)
•
No protection function has picked up
•
This condition persists for a settable time
T V-Supervision
(default setting: 3 s).
The time
T V-Supervision
is required to prevent that a voltage failure is detected before the protection
picks up.
If this monitoring function picks up, the indication
Fail V absent
(no. 168) is generated. The effect of this
monitoring indication is described in the following section “Impact of the Measuring Voltage Failure”.
[lo-zusaetzl-messspgausfall-110428, 1, en_US]
Figure 2-71
Logic diagram of the additional measuring-voltage failure detection
Fail V absent
Impact of the Measuring Voltage Failure
In the event of a measuring voltage failure due to a short circuit or a broken conductor in the voltage trans-
former secondary circuit, individual or all measuring loops may mistakenly see a voltage of zero. Simultane-
ously existing load currents may then cause spurious pickup. When such a measuring voltage failure is
detected, those protection functions are blocked whose measuring principle is based on undervoltage. The
definite time overcurrent protection as emergency function is possible during voltage failure, provided that
the time overcurrent protection is parameterized accordingly (refer to Section
). In the
event of a measuring voltage failure due to a short circuit or a broken conductor in the voltage transformer
Functions
2.14 Monitoring Functions
SIPROTEC 4, 7SD80, Manual
157
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...