Time Overcurrent Protection
Operating Modes
As emergency overcurrent protection or backup overcurrent protection
Emergency Overcurrent Protection
Effective when the differential protection system is blocked (e.g. because of a
failure of the device communication)
Backup overcurrent protection
operates independent of any events
Characteristic Curves
Definite dime stages (definite)
50-B2, 50N-B2, 50-B1, 50N-B1, 50-3, 50N-3, 67-B2, 67N-B2, 67-B1, 67N-B1
(
Ι
Ph
>, 3
Ι
0
>,
Ι
Ph
>>, 3
Ι
0
>>,
Ι
Ph
>>>, 3
Ι
0
>>>,
Ι
Ph
>
dir
, 3
Ι
0
>
dir
,
Ι
Ph
>>
dir
, 3
Ι
0
>>
dir
)
Inverse time elements
51-B, 51N-B, 67-TOC, 67N-TOC
(
Ι
P
, 3
Ι
0P
;
Ι
Pdir
, 3
Ι
0Pdir
); a characteristic curve according to
High-Set Current Elements
Pickup value
50-B1 PICKUP
(phases)
for
Ι
Nom
= 1 A
0.10 A to 25.00 A
or ∞ (ineffective)
Increments 0.01 A
for
Ι
Nom
= 5 A
0.50 A to 125.00 A
or ∞ (ineffective)
Pickup value
50N-B1 PICKUP
(ground)
for
Ι
Nom
= 1 A
0.05 A to 25.00 A
or ∞ (ineffective)
Increments0.01 A
for
Ι
Nom
= 5 A
0.25 A to 125.00 A
or ∞ (ineffective)
Pickup value
67-B1 PICKUP
(directional phases)
for
Ι
Nom
= 1 A
0.10 A to 25.00 A
or ∞ (ineffective)
Increments 0.01 A
for
Ι
Nom
= 5 A
0.50 A to 125.00 A
or ∞ (ineffective)
Delays
(directional phases)
67-B1 DELAY
0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
67N-B1 DELAY
0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
Delay
50-B1 DELAY
(phases)
0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
Delay
50N-B1 DELAY
(ground)
0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
Dropout ratio
approx. 0.93 for
Ι
/
Ι
Nom
≥ 0.5
Pickup times
minimum
30 ms
typical
32 ms
maximum
35 ms
Dropout times
minimum
33 ms
typical
35 ms
maximum
38 ms
Tolerances
Currents
3 % of setting value or 1 % Nennstrom
Times
1 % of setting value or 10 ms
The set times are pure time delays
4.7
Technical Data
4.7 Time Overcurrent Protection
SIPROTEC 4, 7SD80, Manual
267
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...