Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
0
P.U. THRESHOLD
Flx
0.03 .. 40.00 A
2.00 A
Pickup Threshold
0
P.U. THRESHOLD
Flx
1A
0.03 .. 40.00 A
2.00 A
Pickup Threshold
5A
0.15 .. 200.00 A
10.00 A
0
P.U. THRESHOLD
Flx
0.001 .. 1.500 A
0.100 A
Pickup Threshold
0
P.U. THRESHOLD
Flx
2.0 .. 260.0 V
110.0 V
Pickup Threshold
0
P.U. THRESHOLD
Flx
40.00 .. 60.00 Hz
51.00 Hz
Pickup Threshold
0
P.U. THRESHOLD
Flx
50.00 .. 70.00 Hz
61.00 Hz
Pickup Threshold
0
P.U. THRESHOLD
Flx
0.10 .. 20.00 Hz/s
5.00 Hz/s
Pickup Threshold
0
P.U. THRESHOLD
Flx
1A
0.5 .. 10000.0 W
200.0 W
Pickup Threshold
5A
2.5 .. 50000.0 W
1000.0 W
0
P.U. THRESHOLD
Flx
-0.99 .. 0.99
0.50
Pickup Threshold
0
P.U. THRESHOLD
Flx
15 .. 100 %
20 %
Pickup Threshold
0
T TRIP DELAY
Flx
0.00 .. 3600.00 sec 1.00 sec
Trip Time Delay
0
T PICKUP DELAY
Flx
0.00 .. 60.00 sec
0.00 sec
Pickup Time Delay
0
T PICKUP DELAY
Flx
0.00 .. 60.00 sec
0.00 sec
Pickup Time Delay
0A
T DROPOUT DELAY Flx
0.00 .. 60.00 sec
0.00 sec
Dropout Time Delay
0A
BLK.by Vol.Loss
Flx
NO
YES
YES
Block in case of Meas.-
Voltage Loss
0A
DROPOUT RATIO
Flx
0.70 .. 0.99
0.95
Dropout Ratio
0A
DROPOUT RATIO
Flx
1.01 .. 3.00
1.05
Dropout Ratio
0A
DO differential
Flx
0.02 .. 1.00 Hz
0.02 Hz
Dropout differential
201
CT Starpoint
P.System Data
1
towards Line
towards Busbar
towards Line
CT Starpoint
203
Vnom PRIMARY
P.System Data
1
0.4 .. 500.0 kV
10.0 kV
Rated Primary Voltage
204
Vnom SECONDARY P.System Data
1
80 .. 125 V
100 V
Rated Secondary Voltage
(Ph-Ph)
205
CT PRIMARY
P.System Data
1
10 .. 20000 A
400 A
CT Rated Primary Current
206
CT SECONDARY
P.System Data
1
1A
5A
1A
CT Rated Secondary
Current
207
SystemStarpoint
P.System Data
1
Grounded
Peterson-C.Gnd.
Isolated
Grounded
System Starpoint is
220
I4 transformer
P.System Data
1
Not connected
In prot. line
In prot. line
I4 current transformer is
221
I4/Iph CT
P.System Data
1
0.010 .. 5.000
1.000
Matching ratio I4/Iph for
CT's
230
Rated Frequency
P.System Data
1
50 Hz
60 Hz
50 Hz
Rated Frequency
240A TMin TRIP CMD
P.System Data
1
0.02 .. 30.00 sec
0.10 sec
Minimum TRIP Command
Duration
241A TMax CLOSE CMD
P.System Data
1
0.01 .. 30.00 sec
1.00 sec
Maximum Close
Command Duration
242
T-CBtest-dead
P.System Data
1
0.00 .. 30.00 sec
0.10 sec
Dead Time for CB test-
autoreclosure
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SD80, Manual
337
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...