Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
2618 67(N)-B1 Pil/BI
Back-Up O/C
NO
YES
NO
Instantaneous trip via
Pilot Prot./BI
2620 Op.Mode50(N)-B2 Back-Up O/C
ON
Only Emer. prot
OFF
Only Emer. prot
Operating Mode 50(N)-B2
2620 Op.Mode67(N)-B2 Back-Up O/C
ON
Only Emer. prot
OFF
Only Emer. prot
Operating Mode 67(N)-B2
2621 67(N)-B2 Dir.
Back-Up O/C
Non-Directional
Forward
Reverse
Non-Directional
67(N)-B2 Direction
2622 67(N)-B2 on FFM
Back-Up O/C
Non-Directional
BLOCKED
BLOCKED
67(N)-B2 Direct. stage on
Fuse Failure
2623 50-B2 PICKUP
Back-Up O/C
1A
0.10 .. 25.00 A; ∞
1.50 A
50-B2 Pickup
5A
0.50 .. 125.00 A; ∞ 7.50 A
2623 67-B2 PICKUP
Back-Up O/C
1A
0.10 .. 25.00 A; ∞
1.50 A
67-B2 Pickup threshold
5A
0.50 .. 125.00 A; ∞ 7.50 A
2624 50-B2 DELAY
Back-Up O/C
0.00 .. 30.00 sec; ∞ 0.50 sec
50-B2 Delay
2624 67-B2 DELAY
Back-Up O/C
0.00 .. 30.00 sec; ∞ 0.50 sec
67-B2 set time delay
2625 50-B2 Inrush
Back-Up O/C
NO
YES
NO
50-B2 Inrush blocking
2625 67-B2 Inrush
Back-Up O/C
NO
YES
NO
67-B2 Inrush blocking
2626 50N-B2 PICKUP
Back-Up O/C
1A
0.05 .. 25.00 A; ∞
0.20 A
50N-B2 Pickup
5A
0.25 .. 125.00 A; ∞ 1.00 A
2626 67N-B2 PICKUP
Back-Up O/C
1A
0.05 .. 25.00 A; ∞
0.20 A
67N-B2 Pickup threshold
5A
0.25 .. 125.00 A; ∞ 1.00 A
2627 50N-B2 DELAY
Back-Up O/C
0.00 .. 30.00 sec; ∞ 2.00 sec
50N-B2 Delay
2627 67N-B2 DELAY
Back-Up O/C
0.00 .. 30.00 sec; ∞ 2.00 sec
67N-B2 set time delay
2628 50(N)-B2 Pil/BI
Back-Up O/C
NO
YES
NO
Instantaneous trip via
Pilot Prot./BI
2628 67(N)-B2 Pil/BI
Back-Up O/C
NO
YES
NO
Instantaneous trip via
Pilot Prot./BI
2630 Op.Mode 51(N)-B
Back-Up O/C
ON
Only Emer. prot
OFF
OFF
Operating Mode 51(N)-B
2630 Op.Mode67(N)TOC Back-Up O/C
ON
Only Emer. prot
OFF
OFF
Operating Mode 67(N)-
TOC
2631 67(N)-TOC Dir.
Back-Up O/C
Non-Directional
Forward
Reverse
Non-Directional
67(N)-TOC Direction
2632 67(N)-TOCon FFM Back-Up O/C
Non-Directional
BLOCKED
BLOCKED
67(N)-TOC Direct. stage
on Fuse Failure
2633 51-B PICKUP
Back-Up O/C
1A
0.10 .. 4.00 A; ∞
∞ A
51-B Pickup
5A
0.50 .. 20.00 A; ∞
∞ A
2633 67-TOC PICKUP
Back-Up O/C
1A
0.10 .. 4.00 A; ∞
∞ A
67-TOC Pickup threshold
5A
0.50 .. 20.00 A; ∞
∞ A
Functions, Settings, Information
F.2 Settings
342
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...