Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
2905A BAL. FACTOR I
Meas-
urem.Superv
0.10 .. 0.95
0.50
Balance Factor for Current
Monitor
2906A Σ I THRESHOLD
Meas-
urem.Superv
1A
0.10 .. 2.00 A
0.25 A
Summated Current Moni-
toring Threshold
5A
0.50 .. 10.00 A
1.25 A
2907A Σ I FACTOR
Meas-
urem.Superv
0.00 .. 0.95
0.50
Summated Current Moni-
toring Factor
2908A T BAL. V LIMIT
Meas-
urem.Superv
5 .. 100 sec
5 sec
T Balance Factor for
Voltage Monitor
2909A T BAL. I LIMIT
Meas-
urem.Superv
5 .. 100 sec
5 sec
T Current Balance
Monitor
2910 FUSE FAIL MON.
Meas-
urem.Superv
ON
OFF
ON
Fuse Failure Monitor
2911A FFM V>(min)
Meas-
urem.Superv
10 .. 100 V
30 V
Minimum Voltage
Threshold V>
2912A FFM I< (max)
Meas-
urem.Superv
1A
0.10 .. 1.00 A
0.10 A
Maximum Current
Threshold I<
5A
0.50 .. 5.00 A
0.50 A
2913A FFM V<max (3ph)
Meas-
urem.Superv
2 .. 100 V
5 V
Maximum Voltage
Threshold V< (3phase)
2914A FFM Idiff (3ph)
Meas-
urem.Superv
1A
0.05 .. 1.00 A
0.10 A
Differential Current
Threshold (3phase)
5A
0.25 .. 5.00 A
0.50 A
2915 V-Supervision
Meas-
urem.Superv
w/ CURR.SUP
w/ I> & 52a
OFF
w/ CURR.SUP
Voltage Failure Supervi-
sion
2916A T V-Supervision
Meas-
urem.Superv
0.00 .. 30.00 sec
3.00 sec
Delay Voltage Failure
Supervision
2931 BROKEN WIRE
Meas-
urem.Superv
ON
OFF
Alarm only
OFF
Fast broken current-wire
supervision
2933 FAST Σ i SUPERV
Meas-
urem.Superv
ON
OFF
ON
State of fast current
summation supervis
2935A ΔI min
Meas-
urem.Superv
1A
0.05 .. 1.00 A
0.10 A
Min. current diff. for wire
break det.
5A
0.25 .. 5.00 A
0.50 A
3401 FCT 79
79 Auto Recl.
OFF
ON
ON
79 Auto-Reclose Function
3402 52? 1.TRIP
79 Auto Recl.
YES
NO
NO
52-ready interrogation at
1st trip
3403 T-RECLAIM
79 Auto Recl.
0.50 .. 300.00 sec
3.00 sec
Reclaim time after
successful AR cycle
3404 BLOCK MC Dur.
79 Auto Recl.
0.50 .. 300.00 sec;
0
1.00 sec
AR blocking duration after
manual close
3406 EV. FLT. RECOG.
79 Auto Recl.
with PICKUP
with TRIP
with TRIP
Evolving fault recognition
3407 EV. FLT. MODE
79 Auto Recl.
Stops 79
starts 3p AR
is ignored
starts 3p AR
Evolving fault (during the
dead time)
3408 T-Start MONITOR
79 Auto Recl.
0.01 .. 300.00 sec
0.50 sec
AR start-signal monitoring
time
3409 CB TIME OUT
79 Auto Recl.
0.01 .. 300.00 sec
3.00 sec
Circuit Breaker (CB)
Supervision Time
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SD80, Manual
345
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...