Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
3410 RemoteCl. Delay
79 Auto Recl.
0.00 .. 300.00 sec;
∞
0.20 sec
Send delay for remote
close command
3411A Max. DEAD EXT.
79 Auto Recl.
0.50 .. 300.00 sec;
∞
∞ sec
Maximum dead time
extension
3420 AR WITH DIFF
79 Auto Recl.
YES
NO
YES
AR with differential
protection ?
3423 AR w/ INT.TRIP
79 Auto Recl.
YES
NO
YES
AR with intertrip ?
3424 AR w/ DTT
79 Auto Recl.
YES
NO
YES
AR with DTT (direct
transfer trip)
3425 AR w/ 50(N)-B
79 Auto Recl.
YES
NO
YES
AR with 50(N)-B (back-up
overcurrent)
3450 1.AR:START
79 Auto Recl.
YES
NO
YES
Start of AR allowed in this
cycle
3451 1.AR:ActionTime
79 Auto Recl.
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3453 1.AR:DeadT.1Flt
79 Auto Recl.
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase
faults
3454 1.AR:DeadT.2Flt
79 Auto Recl.
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase
faults
3455 1.AR:DeadT.3Flt
79 Auto Recl.
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase
faults
3457 1.AR:Dead 3Trip
79 Auto Recl.
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3458 1.AR:DeadT.EV.
79 Auto Recl.
0.01 .. 1800.00 sec 1.20 sec
Dead time after evolving
fault
3459 1.AR:52? CLOSE
79 Auto Recl.
YES
NO
NO
52-ready interrogation
before reclosing
3461 2.AR:START
79 Auto Recl.
YES
NO
NO
AR start allowed in this
cycle
3462 2.AR:ActionTime
79 Auto Recl.
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3464 2.AR:DeadT.1Flt
79 Auto Recl.
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase
faults
3465 2.AR:DeadT.2Flt
79 Auto Recl.
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase
faults
3466 2.AR:DeadT.3Flt
79 Auto Recl.
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase
faults
3468 2.AR:Dead 3Trip
79 Auto Recl.
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3469 2.AR:DeadT.EV.
79 Auto Recl.
0.01 .. 1800.00 sec 1.20 sec
Dead time after evolving
fault
3470 2.AR:52? CLOSE
79 Auto Recl.
YES
NO
NO
52-ready interrogation
before reclosing
3601 81 O/U FREQ. f1
81 O/U Freq.
ON: Alarm only
ON: with Trip
OFF
ON: Alarm only
81 Over/Under Frequency
Prot. element f1
3602 81-1 PICKUP
81 O/U Freq.
45.50 .. 54.50 Hz
49.50 Hz
81-1 Pickup
3603 81-1 PICKUP
81 O/U Freq.
55.50 .. 64.50 Hz
59.50 Hz
81-1 Pickup
3604 81-1 DELAY
81 O/U Freq.
0.00 .. 600.00 sec
60.00 sec
81-1 Time Delay
Functions, Settings, Information
F.2 Settings
346
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...