[polung-stromwandler-020313-kn, 1, en_US]
Figure 2-2
Polarity of current transformers
Nominal Values of Transformers
In addresses 203
Vnom PRIMARY
and 204
Vnom SECONDARY
the device obtains information on the primary
and secondary rated voltage (phase-to-phase voltage) of the voltage transformers and in addresses 205
CT
PRIMARY
and 206
CT SECONDARY
the information on the primary and secondary rated current of the current
transformers (phases).
The voltage connection is required for all functions that work on the basis of power or voltage values, e.g.
ground fault differential protection in resonant-grounded/isolated systems, directional overcurrent protection,
voltage protection, frequency protection, and to display and record the voltages.
Please make sure that the rated secondary transformer current matches the rated current of the device.
Correct entry of the primary data is a prerequisite for the correct computation of operational measured values
with primary magnitude. If the settings of the device are performed with primary values using DIGSI, these
primary data are an indispensable requirement for the correct function of the device.
Current Connection
The device features four current measurement inputs, three of which are connected to the set of current
transformers. Various possibilities exist for the fourth current input
Ι
4
:
•
Connection of the
Ι
4
input to the ground current in the neutral point of the set of current transformers on
the protected feeder (normal connection, see Appendix
):
Address 220 is then set to:
I4 transformer
=
In prot. line
and address 221
I4/Iph CT
= 1.
•
Connection of the
Ι
4
input to a separate ground current transformer on the protected line (e.g. a summa-
tion CT or core balance CT, see Appendix
):
Address 220 is then set to:
I4 transformer
=
In prot. line
and Address 221
I4/Iph CT
is set:
[uebersetzung-erd-phase-260702-wlk, 1, en_US]
Example:
Phase current transformers 500 A / 5 A
Core balance 60 A / 1 A
[formel-strmwdl-parallelschlt-270702-wlk, 1, en_US]
Functions
2.1 General
SIPROTEC 4, 7SD80, Manual
37
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...