If the pickup is successful, an internal pickup signal is transmitted to the other device.
The element
Ι
dyn is blocked if the frequency deviates by more than 10 % from the rated frequency.
The function is blocked if the communication between the two devices at the ends of the protected object
fails for more than two measuring cycles.
This function can also be blocked via binary input
>87L block
.
The following figure shows the formation of the phase-specific pickup of the elements
87L Isteady>
and
87L Idyn>
.
[lo-pvl-anr-20101117, 1, en_US]
Figure 2-5
Logic diagram of the phase comparison protection, phase-selective generation of the
Ι
stat and
Ι
dyn signal
The pickup signals created locally, signs of idyn and istat and the blocking information are sent to the device at
the opposite end.
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
50
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...