Addr.
Parameter
C
Setting Options
Default Setting
Comments
1233
CT Err. I1
0.003 .. 1.600 A
0.050 A
Current I1 for CT Angle
Error
1234
CT Err. F1
0.0 .. 5.0 °
0.0 °
CT Angle Error at I1
1235
CT Err. I2
0.003 .. 1.600 A
1.000 A
Current I2 for CT Angle
Error
1236
CT Err. F2
0.0 .. 5.0 °
0.0 °
CT Angle Error at I2
1237
87NL:Inrush blk
NO
YES
NO
Inrush blocking
Information List
No.
Information
Type of
Informa-
tion
Comments
3190
Test 87
IntSP
87 Set test state of 87
3191
Commiss.87
IntSP
87 Set Commissioning state of 87
3192
Test 87 remote
OUT
87 Remote relay in test state
3193
Comm. 87 active
OUT
87 Commissioning state is active
3197
>Test 87 ON
SP
87 >Set test state of 87
3198
>Test 87 OFF
SP
87 >Reset test state of 87
3199
Test 87 ON/off
IntSP
87 Test state of 87 ON/OFF
3200
Test 87 ONoffBI
IntSP
87 Test state ON/OFF via BI
3260
>Comm. 87 ON
SP
87 >Commissioning state ON
3261
>Comm. 87 OFF
SP
87 >Commissioning state OFF
3262
Comm 87 ON/OFF
IntSP
87 Commissioning state ON/OFF
3263
Comm 87 ONoffBI
IntSP
87 Commissioning state ON/OFF via BI
32100
>87L block
SP
>87L Protection blocking signal
32102
87L active
OUT
87L Protection is active
32103
87L Fault A
OUT
87L Fault detection A
32104
87L Fault B
OUT
87L Fault detection B
32105
87L Fault C
OUT
87L Fault detection C
32107
87L is blocked
OUT
87L Protection is blocked
32108
87L is OFF
OUT
87L Protection is switched off
32109
87L allow A
OUT
87L A released
32110
87L allow B
OUT
87L B released
32111
87L allow C
OUT
87L C released
32112
87 CTRatioAlarm
OUT
87 CT primary ratio is too high
32113
87L receive blk
OUT
87L receive blocking
32114
87L send blk
OUT
87L send blocking
32115
87L IDYN> A
OUT
87L IDYN> A
32116
87L IDYN> B
OUT
87L IDYN> B
32117
87L IDYN> C
OUT
87L IDYN> C
32118
87L ISTAT> A
OUT
87L ISTAT> A
32119
87L ISTAT> B
OUT
87L ISTAT> B
32120
>87N L block
SP
>87N L Protection blocking signal
32121
>87N L active
OUT
>87N L: Protection is active
32122
87(N)L Gen.Flt.
OUT
87(N)L Fault detection
32124
>87N L I> Flt.
OUT
>87N L: Fault detection of I-Diff>
2.2.6.2
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
64
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...