Table 2-2
Pickup signals of the single phases
Internal indication
Display
Output indication
No.
67-1 PU A
67-2 PU A
67-TOC PU A
67 Pickup ØA
17536
67-1 PU B
67-2 PU B
67-TOC PU B
67 Pickup ØB
17537
67-1 PU C
67-2 PU C
67-TOC PU C
67 Pickup ØC
17538
67-1 PU N
67-2 PU N
67-TOC PU N
67N Pickup Gnd
17539
67-1 PU A
67-1 PU B
67-1 PU C
67-1 PU N
67(N)-B2 PICKUP
7251
67-2 PU A
67-2 PU B
67-2 PU C
67-2 PU N
67(N)-B1 PICKUP
7250
67-TOC PU A
67-TOC PU B
67-TOC PU C
67-TOC PU N
67(N)-TOC PICK.
7252
(All pickups)
67(N) PICKUP
17535
The trip is signaled specifically for each element, e.g.
67(N)-B2 TRIP
.
i
i
NOTE
There is no indication for tripping of the grounding stages. If you need information link the internal pickup
signal with the OFF command of the stage, e.g, 67-1 PU N and
67(N)-B2 TRIP
Behavior during Measuring Voltage Failure
An element-specific parameter, e.g.
67(N)-B1 on FFM
allows you to define how the directional overcurrent
protection acts when the measuring voltage fails. The overcurrent protection then works either
Non-Direc-
tional
or it is BLOCKED.
Setting Notes
General
The setting notes described in the following apply to non-directional and directional overcurrent protection.
Operating Modes
You set the operating mode of the overcurrent protection elements specifically for each element. The setting
applies collectively to the corresponding phase and ground element.
50-1, 3I0>
address 2620
2.4.4
Functions
2.4 Backup overcurrent
82
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...