Example::
Belted cable 10 kV 150 mm
2
Permissible continuous current
Ι
max
= 322 A
Current transformers 400 A/5 A
[formel-therm-ueberl-k-fakt-2-oz-020802, 1, en_US]
Setting value
49 K-FACTOR
= 0.80
Time Constant
The thermal time constant τ
th
is set at address 4203
TIME CONSTANT
. This is also provided by the manufac-
turer. Please note that the time constant is set in minutes. Quite often other values for determining the time
constant are stated which can be converted into the time constant as follows:
1-s current
[fo_perm_1.0-s-continuous-current, 1, en_US]
permissible current for application time other than 1 s, e.g. for 0.5 s
[fo_perm_0.5-s-continuous-current, 1, en_US]
t
6
time; this is the time in seconds for which a current of 6 times the rated current of the protected object may
flow
[formel-therm-ueberl-zeitkonst-3-oz-020802, 1, en_US]
Example::
Cable as above with
Permissible 1-s current 13.5 kA
[formel-therm-ueberl-zeitkonst-4-oz-020802, 1, en_US]
Setting value
TIME CONSTANT
= 29,4 min
Warning Temperature Level
By setting a thermal alarm stage
49 Θ ALARM
(address 4204) an alarm can be provided before the tripping
temperature is reached, so that a trip can be avoided by preventive load reduction or by switching over. The
percentage is referred to the tripping temperature rise.
The current overload alarm setpoint
I ALARM
(address 4205) is stated as a factor of the nominal device
current and should be set equal to or slightly below the permissible continuous current k · IN. It can also be
used instead of the thermal alarm stage. In this case the thermal alarm stage is set to 100 % and thus practi-
cally ineffective.
Functions
2.7 Thermal Overload Protection 49
106
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...