Renaming Messages, Checking Configurations
After parameterization of a flexible function, the following steps should be noted:
•
Open matrix in DIGSI
•
Rename the neutral message texts in accordance with the application.
•
Check configurations on contacts and in operation and fault buffer, or set them according to the require-
ments.
Further Information
The following instruction should be noted:
•
As the power factor does not differentiate between capacitive and inductive, the sign of the reactive
power may be used with CFC-help as an additional criterion.
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding
secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
0
FLEXIBLE FUNC.
OFF
ON
Alarm Only
OFF
Flexible Function
0
OPERRAT. MODE
3-phase
1-phase
no reference
3-phase
Mode of Operation
0
MEAS. QUANTITY
Please select
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
Frequency
df/dt rising
df/dt falling
Binary Input
Please select
Selection of Measured
Quantity
0
MEAS. METHOD
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Fundamental
Selection of Measurement
Method
0
PICKUP WITH
Exceeding
Dropping below
Exceeding
Pickup with
0
CURRENT
Ia
Ib
Ic
In
In sensitive
Ia
Current
2.15.3
Functions
2.15 Flexible Protection Functions
174
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...