Differential Protection Values
Measured Values of the Differential Protection
The differential and restraint current values of the differential protection can be displayed at the front of the
device, read out via the operating interface using a PC with DIGSI, or transferred to a control center via the
system interface.
Table 2-11
Messwerte des Differentialschutzes
Measured Values
referred to
Diff3I0=
Calculated restraint currents of the zero sequence system
% rated operational current
Rest3I0=
Calculated differential current of the zero sequence system
Ι
/
Ι
nO
Information List
No.
Information
Type of
Informa-
tion
Comments
7748
Diff3I0=
MV
Diff3I0 (Differential current 3I0)
32226
Rest3I0=
MV
Rest3I0(% Operational nominal current)
Measured Values Constellation
Functional Description
The measured values of the constellation of both possible devices are shown here by evaluating the device
(see
). Information on the second device is given in the Appendix.
The computation of this measured values constellation is also executed during an existent system fault in an
interval of approx. 0.5 s.
The current/voltage measured locally is assumed as reference value for the angle. The angle values of the
remote ends are referred to the locally measured value.
Examples for the current in a constellation with 2 ends:
Current
Ι
A at the local end 98 % angle 0°
Current
Ι
A at the local end 98 % angle 180°
The device addresses allow differentiating the devices. This procedure allows current transformer polarity
reversal to be detected immediately and the line angle (if voltages are available) to be read.
2.17.4
2.17.4.1
2.17.4.2
2.17.5
2.17.5.1
Functions
2.17 Auxiliary Functions
186
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...