[objekteigenschaft-verriegelungsbeding-020313-kn, 1, en_US]
Figure 2-85
DIGSI dialog box for setting the interlocking conditions
On devices with operator panel, the display shows the configured interlocking reasons. They are marked with
letters explained in the following table.
Table 2-14
Command types and corresponding messages
Interlocking Commands
Abbrev.
Display
Switching Authority
L
L
System interlocking
S
A
Zone controlled
Z
Z
SET = ACTUAL (switch direction check)
P
P
Protection blocking
B
B
Control Logic using CFC
For bay interlocking, a release logic can be created using CFC. Via specific release conditions the information
"released" or "bay interlocked" are available (e.g. object "52 Close" and "52 Open" with the data values: ON/
OFF).
Switching Authority
The interlocking condition "Switching Authority" serves for determining the switching authority. It enables the
user to select the authorized command source. For devices with operator panel, the following switching
authority ranges are defined in the following priority sequence:
•
LOCAL
•
DIGSI
•
REMOTE
Functions
2.18 Breaker Control
SIPROTEC 4, 7SD80, Manual
199
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...