Connect a solid low-ohmic protective and operational ground to the grounding terminal of the device.
The cross-section of the cable used must correspond to the maximum connected cross-section but must
be at least 2.5 mm
2
(Grounding area > M4, grounding area to be lacquer-free).
•
Connections are to be established via the screw terminals at the rear panel of the device in accordance
with the circuit diagram. The details on the connection technique for the communication modules on the
bottom of the device (port A and port B) in accordance with the SIPROTEC 4 System Description and the
details on the connection technique for the current and voltage terminals at the rear of the device in the
Sections “Connections of the Current Terminals” and “Connections of the Voltage Terminals” must be
strictly observed.
[montage-7sj8x-einsechstel-gehaeuse-20070117, 1, en_US]
Figure 3-13
Example installation of a 7SD80 in a rack or cubicle
Panel Surface Mounting
When ordering the device as surface-mounting case (9th digit of the ordering number= B), the mounting
frame shown below is part of the scope of delivery.
For installation, proceed as follows:
•
Drill the holes for the mounting frame into the control panel.
•
Fasten the mounting frame with 4 screws to the control panel (the continuously open side of the
mounting frame is intended for the cable harnesses and can point at the top or bottom according to
customer specification).
•
Loosen the terminal blocks for the wiring, wire the terminal blocks and then click them in again.
•
Connect a solid low-ohmic protective and operational ground to the grounding terminal of the device.
The cross-section of the cable used must correspond to the maximum connected cross-section but must
be at least 2.5 mm
2
(Grounding area > M4, grounding area to be lacquer-free).
3.1.3.4
Mounting and Commissioning
3.1 Mounting and Connections
220
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...