[dsub-buchsen-20070111, 1, en_US]
Figure 3-18
Serial interface at the device bottom
USB Interface
The USB interface can be used to establish a connection between the protection device and your PC. For the
communication, the Microsoft Windows USB driver is used which is installed together with DIGSI (as of version
V4.82). The interface is installed as a virtual serial COM port. We recommend the use of standard USB cables
with a maximum length of 5 m/16 ft.
Table 3-2
Assignment of the USB socket
Pin-No.
1
2
3
4
Housing
USB
VBUS
(unused)
D-
D+
GND
Shield
Connections at Port A
Protection data interface optical fiber cable with LC duplex connector.
The order numbers of the exchange modules are listed in the Appendix in Section
, Accessories.
Connections at port B
Table 3-3
Assignments of the port B sockets
Pin-No. RS232 RS232 time
synchroni-
zation
2)
RS485
Profibus DP,
RS485
Modbus
RS485
DNP3.0
RS485
Ethernet
EN 100
IEC 60870–5–
103
redundant
1
Shield (with shield ends electrically connected)
Tx+
B/B’ (RxD/TxD-P)
2
RxD
–
–
–
–
Tx–
A/A’ (RxD/TxD-N)
3
TxD
–
A/A’ (RxD/TxD-N)
B/B’ (RxD/TxD-P)
A
Rx+
–
4
–
–
–
CNTR-A (TTL)
RTS (TTL
level)
—
–
5
GND
GND
C/C’ (GND)
C/C’ (GND)
GND1
—
–
6
–
–
–
+5 V ((max. load
<100 mA)
VCC1
Rx–
–
7
RTS
–
–
1)
–
–
—
–
8
CTS
CTS
B/B’ (RxD/TxD-P)
A/A’ (RxD/TxD-N)
B
—
–
9
–
–
–
–
–
not available
not available
1)
Pin 7 trägt auch bei Betrieb als RS485-Schnittstelle das Signal RTS mit RS232-Pegel. Pin 7 darf deshalb nicht anges-
chlossen werden!
2)
Für Zeitsynchronisation über RS232 ist die Steckbrücke X11 in Stellung 1-2 nötig.
Mounting and Commissioning
3.2 Checking Connections
SIPROTEC 4, 7SD80, Manual
223
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...