Humidity
Permissible humidity
Mean value per year ≤ 75 % relative humidity;
on 56 days of the year up to 93 % relative humidity;
condensation must be avoided!
Siemens recommends that all devices be installed such that they are not exposed to direct sunlight, nor
subject to large fluctuations in temperature that may cause condensation to occur.
Service Conditions
The protective device is designed for use in an industrial environment and an electrical utility environment.
Proper installation procedures should be followed to ensure electromagnetic compatibility (EMC).
In addition, the following is recommended:
•
All contacts and relays that operate in the same cubicle, cabinet, or relay panel as the numerical protec-
tive device should, as a rule, be equipped with suitable surge suppression components.
•
For substations with operating voltages of 100 kV and above, all external cables should be shielded with
a conductive shield grounded at both ends. For substations with lower operating voltages, no special
measures are normally required.
•
Do not withdraw or insert individual modules or boards while the protective device is energized. In with-
drawn condition, some components are electrostatically endangered; during handling the ESD stand-
ards (for Electrostatic Sensitive Devices) must be observed. They are not endangered when inserted into
the case.
Design
Case
7XP20
Dimensions
see dimensional drawings, Section
Device
Case
Size
Weight
7SD80**-*B
for panel surface mounting
1
/
6
4.5 kg
7SD80**-*E
for panel flush mounting
1
/
6
4 kg
Protection type acc. to IEC 60529
for equipment in the surface-mounting case
IP 50
for equipment in flush mounting case
Front IP 51
Rear IP 50
for operator protection
IP 2x for current terminal
IP 1x for voltage terminal
Degree of pollution, IEC 60255-27
2
UL Certification Conditions
Output Relays
DC 24 V
5 A General Purpose
DC 48 V
0,8 A General Purpose
DC 240 V
0.1 A General Purpose
AC 240 V
5 A General Purpose
AC 120 V
1/3 hp
AC 250 V
1/2 hp
B300, R300
Voltage Inputs
Input voltage range
300 V
4.1.8
4.1.9
4.1.10
Technical Data
4.1 General Device Data
SIPROTEC 4, 7SD80, Manual
257
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...