Inrush Current Restraint Breaker Intertrip and Remote Tripping
Phase Comparison Protection
Restraint ratio
2. Harmonische zur Grundschwingung
Ι
2fNom
/
Ι
fNom
0 % to 45 %
Increments 1 %
Max. current for restraint
Ι
Nom
= 1 A
1.1 A to 25.0 A
Increments 0.1 A
Ι
Nom
= 5 A
5.5 A to 125.0 A
Crossblock function
can be switched on/off
Max. action time for crossblock
CROSSB 2HM
0.00 s to 60.00 s
or 0 (crossblock deactivated)
or ∞ (active until dropout)
Increments 0.01 s
Restricted Earth Fault Protection
Restraint ratio
2. Inrush stabilization
Ι
2fNom
/
Ι
fNom
0 % to 45 %
Increments 1 %
Max. current for restraint
Ι
Nom
= 1 A
1.1 A to 25.0 A
Increments 0.1 A
Ι
Nom
= 5 A
5.5 A to 125.0 A
Crossblock function
zu- und abschaltbar
Max. action time for crossblock
CROSSB 2HM
0.00 s to 60.00 s
or 0 (crossblock deactivated)
or ∞ (active until dropout)
Increments 0.01 s
4.8
Technical Data
4.8 Inrush Current Restraint Breaker Intertrip and Remote Tripping
274
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...