Automatic Reclosing (Optional)
Automatic Reclosures
Number of reclosures
max. 2
Type (depending on order variant)
3-pole
Control
with pickup or trip command
Action times
Initiation possible without pickup and action time
0.01 s to 300.00 s; ∞
Increments 0.01 s
Dead times prior to reclosure
separately for all types and all cycles
0.01 s to 1800.00 s; ∞
Increments 0.01 s
Dead times after evolving fault recognition
0.01 s to 1800.00 s
Increments 0.01 s
Blocking time after reclosure
0.50 s to 300.00 s
Increments 0.01 s
Blocking time after dynamic blocking
0.5 s
Blocking time after manual closing
0.50 s to 300.00 s; 0
Increments 0.01 s
Start signal monitoring time
0.01 s to 300.00 s
Increments 0.01 s
Circuit breaker monitoring time
0.01 s to 300.00 s
Increments 0.01 s
4.13
Technical Data
4.13 Automatic Reclosing (Optional)
282
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...