[ansprechkennl-diffschutz-20110526, 1, en_US]
Figure 2-11
Pickup characteristic of the ground differential protection
If it is desired that an internal fault should initiate a TRIP command and additionally a local current of a specific
quantity should exist, the value of this current can be set at address 1225
87N L: I>RELEAS
. The default
setting for this parameter is zero so that this additional criterion does not become effective.
The differential current and the restraint current 3I0diff and 3I0restr are included in the fault record.
Blocking / Interblocking
The ground current differential protection can be blocked via a binary input. The blocking at one end of a
protected object affects all ends via the communications link (interblocking). If the overcurrent protection is
configured as an emergency function, all devices will automatically switch to this emergency operation mode.
Pickup Logic
The following figure illustrates the pickup logic of the ground current differential protection for grounded
systems.
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
56
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...