Breaker Intertrip and Remote Tripping
The 7SD80 device allows transmitting a trip command created by the local differential protection to the other
end of the protected object (intertripping). Likewise, any desired command of another internal protection
function or of an external protection, monitoring or control equipment can be transmitted for remote tripping.
Functional Description
Transmit Circuit
The transmission signal can originate from two different sources (
). If the parameter
85 DT:
SEND
is set to
YES
, each tripping command of the differential protection is routed immediately to the trans-
mission function „ITrp.sen. A“ to "...C“ (intertrip) and transmitted via the protection data interfaces and
communication links.
The send function can be triggered via binary input
>85 DT 3pol
(remote tripping). The transmission signal
can be delayed with
85 DT: TD-BI
and prolonged with
85 DT: TD-BI
.
[lo-mitnahme-sendekreis-20101108, 1, en_US]
Figure 2-24
Logic diagram of the intertrip — Transmission circuit
Receive Circuit
On the receiving end the signal can lead to a trip. Alternatively, it can also cause an alarm only. In this way it is
possible to determine for each end of the protected object whether the received signal is to trip at this partic-
ular end or not.
If the received signal is to cause the trip, it will be forwarded to the tripping logic of the device.
2.3
2.3.1
Functions
2.3 Breaker Intertrip and Remote Tripping
SIPROTEC 4, 7SD80, Manual
69
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...