[logik-strmflsueberw-plausibilitaet-wlk-010802, 1, en_US]
Figure 2-36
Current flow monitoring with plausibility currents 3·
Ι
0
and 3·
Ι
2
1)
only usable/visible if address 139 is set to
vorh. mit 3I0>
In-Phase Start
Common phase initiation is used for transformer feeders or if the busbar protection trips.
If the breaker failure protection is intended to be initiated by further external protection devices, it is recom-
mended, for security reasons, to connect two starting criteria to the device. Besides the trip command of the
external relay to the binary input
>50BF Start 3p
(FNo. 1415) it is recommended to connect also the
general device pickup to binary input
>50BF release
(FNo. 1432). For Buchholz protection it is recom-
mended that the trip command is connected to the device by two separate wire pairs.
Nevertheless, it is possible to initiate the breaker failure protection in single-channel mode should a separate
release criterion not be available. The binary input
>50BF release
(FNo. 1432) must then not be assigned
to any physical input of the device during configuration.
shows the operating principle. When the trip signal appears from any internal or external feeder
protection and at least one current flow criterion (according to
) is present, the breaker failure
protection is initiated and the corresponding time delay(s) is (are) started.
If the current criterion is not satisfied for any of the phases, the circuit-breaker auxiliary contact can be interro-
gated according to
. After a 3-pole trip command, the circuit breaker has only operated correctly
when no current flows over any of the poles.
Functions
2.6 Circuit Breaker Failure Protection 50BF
96
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...