[logikdia-vorwaertsleistungsueberwachung, 1, en_GB]
Figure 2-105
Logic diagram of the forward active power supervision
Setting Notes
General
The application of forward power monitoring is only possible in 3-phase protected objects. It can only be
assigned to a side of the main protected object or another measuring location. Furthermore, it is a prerequisite
that the device is connected to a three-phase voltage transformer set, that permits a sensible calculation of
the active power with the respective current transformer connection.
The forward power monitoring can only be effective and is only accessible if it has been set during configura-
tion under address 151
FORWARD POWER
=
Enabled
Under address 5101
FORWARD POWER
the forward power monitoring can be switched
ON
or
OFF
. Further-
more, the command can be blocked during enabled monitoring function (
Block relay
).
Pickup Values
For undershooting of a preset active power and the exceeding of another preset active power, one pickup
value each must be set.
If the forward power monitoring has been assigned to a side of the protected object, the pickup value can be
set directly as reference value (with reference to the nominal power of the respective side), thus under
address 5112
P< fwd
for undershooting of active power and under address 5115
P> fwd
for exceeding of
active power.
If, however, the forward power monitoring must be set in amps secondary, the active power must be
converted to a secondary value. The settings can then be effected under address 5111
Pf<
for undershooting
of active power and under address 5114
Pf>
for exceeding of active power.
The latter is always the case if the forward power monitoring has been assigned to a measuring location, and
not a side of the main protected object.
The following applies to the conversion:
[flexfkn-ansprechwert-250204-he, 1, en_GB]
2.13.2
Functions
2.13 Forward Power Supervision
230
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...