Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
0
FLEXIBLE FUNC.
OFF
ON
Alarm Only
Block relay
OFF
Flexible Function
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I meas.
location 1
5A
0.25 .. 175.00 A
10.00 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I meas.
location 2
5A
0.25 .. 175.00 A
10.00 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I meas.
location 3
5A
0.25 .. 175.00 A
10.00 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I meas.
location 4
5A
0.25 .. 175.00 A
10.00 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I meas.
location 5
5A
0.25 .. 175.00 A
10.00 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I1
5A
0.25 .. 175.00 A
10.00 A
0.1A 0.005 .. 3.500 A
0.200 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I2
5A
0.25 .. 175.00 A
10.00 A
0.1A 0.005 .. 3.500 A
0.200 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I3
5A
0.25 .. 175.00 A
10.00 A
0.1A 0.005 .. 3.500 A
0.200 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I4
5A
0.25 .. 175.00 A
10.00 A
0.1A 0.005 .. 3.500 A
0.200 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I5
5A
0.25 .. 175.00 A
10.00 A
0.1A 0.005 .. 3.500 A
0.200 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I6
5A
0.25 .. 175.00 A
10.00 A
0.1A 0.005 .. 3.500 A
0.200 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I7
5A
0.25 .. 175.00 A
10.00 A
0.1A 0.005 .. 3.500 A
0.200 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I8
5A
0.25 .. 175.00 A
10.00 A
0.1A 0.005 .. 3.500 A
0.200 A
0
Pick-up thresh.
1A
0.05 .. 35.00 A
2.00 A
Pick-up threshold I9
5A
0.25 .. 175.00 A
10.00 A
0.1A 0.005 .. 3.500 A
0.200 A
2.22.7.3
Functions
2.22 Auxiliary Functions
294
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...