For 1-phase busbar protection:
Each input can be set individually. Only if measuring inputs
Ι
1
to
Ι
3
have the same rated current, X68 is
plugged to the same rated current. Only if measuring inputs
Ι
4
to
Ι
6
have the same rated current, X69 is
plugged to the same rated current.
If different rated currents are reigning within the input groups, the corresponding common jumper is
plugged to“undef”.
For interposed summation transformers with 100 mA output, jumpers of all measuring inputs, including
the common jumpers, are plugged to 0.1 A.
Table 3-11
Assignment of jumpers for the rated current to the measuring inputs
Application
Jumpers
3-phase
1-phase
individual
common
Ι
L1S1
Ι
1
X61
X68
Ι
L2S1
Ι
2
X62
Ι
L3S1
Ι
3
X63
Ι
L1S2
Ι
4
X65
X69
Ι
L2S2
Ι
5
X66
Ι
L3S2
Ι
6
X67
Ι
Z1
Ι
7
X64
X70
Ι
Z3
Ι
8
–
–
Input/Output Board(s) C-I/O-1 and C-I/O-10 (only 7UT633 and 7UT635)
The PCB layout for the C-I/O-1 input/output board is shown in
and the input/output group C-I/O-10
Mounting and Commissioning
3.1 Mounting and Connections
326
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...