Message
No.
Meaning
see
Section
Pf> VT error
5131
Forward power supervision is not available without voltage connec-
tion
Pf> set error
5133
Forward power supervision setting not plausible
BkrFail Not av.
047.2491
Breaker failure protection is not available for the configured protected
object
BkrFail2 Not av
206.2491
Breaker failure protection 2 is not available for the configured
protected object
2.1.4 Power
System Data
12.1.6 Powe
r System
Data 2
TripC ProgFail
6864
For trip circuit supervision the number of binary inputs was set incor-
rectly
(“Connec-
tion
Variants“)”)
Check in the operational or spontaneous annunciations that there is not any information on inconsistencies.
The matching factors of all measured value inputs are indicated in the operational annunciations. It is recom-
mended to check these factors even if none of the above mentioned alarms is present. The indicated factors
are:
•
generally, the ratio of the rated current/voltage of the side referred to the rated current/voltage of the
instrument transformers at the measuring locations;
•
for differential protection, the ratio of the rated current of the protected object referred to the rated
current of the current transformers at the measuring locations;
•
for restricted earth fault protection, the ratio of the rated current of the assigned side of the protected
object referred to the rated current of the starpoint current transformer.
None of these factors should be greater than 8 or smaller than 0.125. Otherwise, the risk of higher measuring
errors could arise. If a factor is greater than 50 or smaller than 0.02, unexpected reactions of protection func-
tion may occur.
Table 3-30
Indications on matching factors
Message
No.
Description
see
section
Gen CT-M1:
to
Gen CT-M5:
30060
to
30064
General: Magnitude matching factor at the indicated measuring loca-
tion
Gen VT-U1:
30065
General: Magnitude matching factor of 3-phase voltage input
Diff CT-M1:
to
Diff CT-M5:
5733
to
5737
Differential protection: Magnitude matching factor of the indicated
measuring location (3-phase protected objects)
Diff CT-I1:
to
DiffCT-I12:
5721
to
5732
Differential protection: Magnitude matching factor of the indicated
measuring location (1-phase busbar protection)
Mounting and Commissioning
3.3 Commissioning
364
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...