Differential Protection
Pickup Values
Differential current
Ι
Diff
>/
Ι
NObj
0.05 to 2.00
Increments 0.01
High-current stage
Ι
Diff
>>/
Ι
NObj
0.5 to 35.0
or ∞ (ineffective)
Increments 0.1
Increase of the pickup value when
connecting as a factor of
Ι
Diff
>
1.0 to 2.0
Increments 0.1
Add-on restraint on external fault
(
Ι
Rest
> setting value)
Action time
Ι
add-on
/
Ι
NObj
2.00 to 15.00
2 to 250 cycles
or ∞ (active until
dropout)
Increments 0.01
Increments 1 cycle
Trip characteristic
see
Tolerances (with preset characteristic parameters, for 2 sides with 1 measuring location
each)
Ι
Diff
>-stage and characteristic
5 % of set value
Ι
Diff
>>-stage
5 % of set value
Time Delays
Delay of
Ι
Diff
>-stage
T
Ι
Diff>
0.00 s to 60.00 s
or ∞ (no trip)
Increments 0.01 s
Delay of
Ι
Diff
>>-stage
T
Ι
Diff>>
0.00 s to 60.00 s
or ∞ (no trip)
Increments 0.01 s
Time tolerance
1 % of set value or 10 ms
The set times are pure delay times
[tdausloesekennliniediff7ut612-021026-rei, 1, en_GB]
Figure 4-1
Tripping characteristic of the differential protection
4.2
Technical Data
4.2 Differential Protection
408
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...