Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
1142 PoleOpenCurrI12
P.System Data
2
1A
0.04 .. 1.00 A
0.04 A
Pole Open Current
Threshold End 12
5A
0.20 .. 5.00 A
0.20 A
0.1
A
0.004 .. 0.100 A
0.004 A
1151 PoleOpenCurrIX1
P.System Data
2
1A
0.04 .. 1.00 A
0.04 A
Pole Open Current
Threshold AuxiliaryCT1
5A
0.20 .. 5.00 A
0.20 A
1152 PoleOpenCurrIX2
P.System Data
2
1A
0.04 .. 1.00 A
0.04 A
Pole Open Current
Threshold AuxiliaryCT2
5A
0.20 .. 5.00 A
0.20 A
1153 PoleOpenCurrIX3
P.System Data
2
1A
0.04 .. 1.00 A
0.04 A
Pole Open Current
Threshold AuxiliaryCT3
5A
0.20 .. 5.00 A
0.20 A
1154 PoleOpenCurrIX4
P.System Data
2
1A
0.04 .. 1.00 A
0.04 A
Pole Open Current
Threshold AuxiliaryCT4
5A
0.20 .. 5.00 A
0.20 A
1201 DIFF. PROT.
Diff. Prot
OFF
ON
Block relay
OFF
Differential Protection
1205 INC.CHAR.START
Diff. Prot
OFF
ON
OFF
Increase of Trip Char.
During Start
1206 INRUSH 2.HARM.
Diff. Prot
OFF
ON
ON
Inrush with 2. Harmonic
Restraint
1207 RESTR. n.HARM.
Diff. Prot
OFF
3. Harmonic
5. Harmonic
OFF
n-th Harmonic Restraint
1208 I-DIFF> MON.
Diff. Prot
OFF
ON
ON
Differential Current moni-
toring
1210 I> CURR. GUARD
Diff. Prot
0.20 .. 2.00 I/InS; 0 0.00 I/InS
I> for Current Guard
1211A DIFFw.IE1-MEAS
Diff. Prot
NO
YES
NO
Diff-Prot. with meas.
Earth Current S1
1212A DIFFw.IE2-MEAS
Diff. Prot
NO
YES
NO
Diff-Prot. with meas.
Earth Current S2
1213A DIFFw.IE3-MEAS
Diff. Prot
NO
YES
NO
Diff-Prot. with meas.
Earth Current S3
1214A DIFFw.IE4-MEAS
Diff. Prot
NO
YES
NO
Diff-Prot. with meas.
Earth Current S4
1215A DIFFw.IE5-MEAS
Diff. Prot
NO
YES
NO
Diff-Prot. with meas.
Earth Current S5
1216A DIFFw.IE3phMEAS Diff. Prot
NO
YES
NO
Diff-Prot.with
meas.current earth.electr
1221 I-DIFF>
Diff. Prot
0.05 .. 2.00 I/InO
0.20 I/InO
Pickup Value of Differen-
tial Curr.
1226A T I-DIFF>
Diff. Prot
0.00 .. 60.00 sec; ∞ 0.00 sec
T I-DIFF> Time Delay
1231 I-DIFF>>
Diff. Prot
0.5 .. 35.0 I/InO; ∞
7.5 I/InO
Pickup Value of High Set
Trip
1236A T I-DIFF>>
Diff. Prot
0.00 .. 60.00 sec; ∞ 0.00 sec
T I-DIFF>> Time Delay
1241A SLOPE 1
Diff. Prot
0.10 .. 0.50
0.25
Slope 1 of Tripping Char-
acteristic
1242A BASE POINT 1
Diff. Prot
0.00 .. 2.00 I/InO
0.00 I/InO
Base Point for Slope 1 of
Charac.
Functions, Settings, Information
F.2 Settings
562
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...