Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
5316 T U>>
Overvoltage
0.00 .. 60.00 sec; ∞ 0.50 sec
T U>> Time Delay
5317A DOUT RATIO
Overvoltage
0.90 .. 0.99
0.98
U>, U>> Drop Out Ratio
5318A VALUES
Overvoltage
U-ph-ph
U-ph-e
U-ph-ph
Measurement Values
5601 O/U FREQUENCY
Frequency Prot.
OFF
ON
Block relay
OFF
Over / Under Frequency
Protection
5611 f<
Frequency Prot.
40.00 .. 49.99 Hz; 0 49.50 Hz
Pick-up frequency f<
5612 f<<
Frequency Prot.
40.00 .. 49.99 Hz; 0 48.00 Hz
Pick-up frequency f<<
5613 f<<<
Frequency Prot.
40.00 .. 49.99 Hz; 0 47.00 Hz
Pick-up frequency f<<<
5614 f>
Frequency Prot.
50.01 .. 66.00 Hz; ∞ 52.00 Hz
Pick-up frequency f>
5621 f<
Frequency Prot.
50.00 .. 59.99 Hz; 0 59.50 Hz
Pick-up frequency f<
5622 f<<
Frequency Prot.
50.00 .. 59.99 Hz; 0 58.00 Hz
Pick-up frequency f<<
5623 f<<<
Frequency Prot.
50.00 .. 59.99 Hz; 0 57.00 Hz
Pick-up frequency f<<<
5624 f>
Frequency Prot.
60.01 .. 66.00 Hz; ∞ 62.00 Hz
Pick-up frequency f>
5631 f<
Frequency Prot.
10.00 .. 16.69 Hz; 0 16.50 Hz
Pick-up frequency f<
5632 f<<
Frequency Prot.
10.00 .. 16.69 Hz; 0 16.00 Hz
Pick-up frequency f<<
5633 f<<<
Frequency Prot.
10.00 .. 16.69 Hz; 0 15.70 Hz
Pick-up frequency f<<<
5634 f>
Frequency Prot.
16.67 .. 22.00 Hz; ∞ 17.40 Hz
Pick-up frequency f>
5641 T f<
Frequency Prot.
0.00 .. 100.00 sec;
∞
20.00 sec
Delay time T f<
5642 T f<<
Frequency Prot.
0.00 .. 600.00 sec;
∞
1.00 sec
Delay time T f<<
5643 T f<<<
Frequency Prot.
0.00 .. 100.00 sec;
∞
6.00 sec
Delay time T f<<<
5644 T f>
Frequency Prot.
0.00 .. 100.00 sec;
∞
10.00 sec
Delay time T f>
5651 Umin
Frequency Prot.
10.0 .. 125.0 V; 0
65.0 V
Minimum Required
Voltage for Operation
5652 U MIN
Frequency Prot.
0.10 .. 1.25 U/UnS;
0
0.65 U/UnS
Minimum voltage
7001 BREAKER FAILURE
Breaker Failure
OFF
ON
Block relay
OFF
Breaker Failure Protection
7011 START WITH REL.
Breaker Failure
0 .. 8
0
Start with Relay (intern)
7012 START WITH REL.
Breaker Failure
0 .. 24
0
Start with Relay (intern)
7015 T1
Breaker Failure
0.00 .. 60.00 sec; ∞ 0.15 sec
T1, Delay of 1st stage
(local trip)
7016 T2
Breaker Failure
0.00 .. 60.00 sec; ∞ 0.30 sec
T2, Delay of 2nd stage
(busbar trip)
7101 BREAKER FAILURE
Breaker Fail. 2
OFF
ON
Block relay
OFF
Breaker Failure Protection
7111 START WITH REL.
Breaker Fail. 2
0 .. 8
0
Start with Relay (intern)
7112 START WITH REL.
Breaker Fail. 2
0 .. 24
0
Start with Relay (intern)
7115 T1
Breaker Fail. 2
0.00 .. 60.00 sec; ∞ 0.15 sec
T1, Delay of 1st stage
(local trip)
7116 T2
Breaker Fail. 2
0.00 .. 60.00 sec; ∞ 0.30 sec
T2, Delay of 2nd stage
(busbar trip)
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7UT6x, Manual
579
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...