Feeder 5
•
Address 601
STRPNT->BUS I5
= transformer starpoint versus busbar for feeder 5,
•
Address 602
IN-PRI CT I5
= rated primary transformer current for feeder 5,
•
Address 603
IN-SEC CT I5
= rated secondary transformer current for feeder 5.
Feeder 6
•
Address 611
STRPNT->BUS I6
= transformer starpoint versus busbar for feeder 6,
•
Address 612
IN-PRI CT I6
= rated primary transformer current for feeder 6,
•
Address 613
IN-SEC CT I6
= rated secondary transformer current for feeder 6.
Feeder 7
•
Address 621
STRPNT->BUS I7
= transformer starpoint versus busbar for feeder 7,
•
Address 622
IN-PRI CT I7
= rated primary transformer current for feeder 7,
•
Address 623
IN-SEC CT I7
= rated secondary transformer current for feeder 7.
The following settings are only available in 7UT613/63x:
Feeder 8
•
Address 631
STRPNT->BUS I8
= transformer starpoint versus busbar for feeder 8,
•
Address 632
IN-PRI CT I8
= rated primary transformer current for feeder 8,
•
Address 633
IN-SEC CT I8
= rated secondary transformer current for feeder 8.
Feeder 9
•
Address 641
STRPNT->BUS I9
= transformer starpoint versus busbar for feeder 9,
•
Address 642
IN-PRI CT I9
= rated primary transformer current for feeder 9,
•
Address 643
IN-SEC CT I9
= rated secondary transformer current for feeder 9.
The following settings are only available in 7UT635:
Feeder 10
•
Address 651
STRPNT->BUS I10
= transformer starpoint versus busbar for feeder 10,
•
Address 652
IN-PRI CT I10
= rated primary transformer current for feeder10,
•
Address 653
IN-SEC CT I10
= rated secondary transformer current for feeder 10.
Feeder 11
•
Address 661
STRPNT->BUS I11
= transformer starpoint versus busbar for feeder 11,
•
Address 662
IN-PRI CT I11
= rated primary transformer current for feeder 11,
•
Address 663
IN-SEC CT I11
= rated secondary transformer current for feeder 11.
Feeder 12
•
Address 671
STRPNT->BUS I12
= transformer starpoint versus busbar for feeder 12,
•
Address 672
IN-PRI CT I12
= rated primary transformer current for feeder 12,
•
Address 673
IN-SEC CT I12
= rated secondary transformer current for feeder 12.
Current Transformer Data for 1-phase Further Current Inputs
The number of 1-phase further current inputs depends on the device version. Such inputs are used for detec-
tion of the starpoint current of an earthed winding of a transformer, generator, or motor, shunt reactor, or
neutral reactor, or for different 1-phase measuring purposes. The assignment has already been carried out in
Section
, margin heading “Assignment of Auxiliary 1-phase Measuring Locations”,
the assignment of the protection functions will be done in Section “Assignment of the Protection Functions to
the Measuring Locations/Sides”. These settings concern exclusively the current transformer data, regardless of
whether or not they belong to the main protected object.
Functions
2.1 General
SIPROTEC 4, 7UT6x, Manual
65
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...