[ausloesebereich-des-uebereregungsschutz-020827-ho, 1, en_GB]
Figure 2-103
Tripping time characteristic of the overexcitation protection
Otherwise, any tripping characteristic can be specified by point-wise entering the delay times for the 8 prede-
fined U/f-values:
Address 4306
t(U/f=1.05)
Adresse 4307
t(U/f=1.10)
Address 4308
t(U/f=1.15)
Address 4309
t(U/f=1.20)
Address 4310
t(U/f=1.25)
Address 4311
t(U/f=1.30)
Address 4312
t(U/f=1.35)
Address 4313
t(U/f=1.40)
Functions
2.11 Overexcitation Protection
SIPROTEC 4, 7UT6x, Manual
221
C53000-G1176-C230-5, Edition 09.2016