Voltage Phase Sequence
If measured voltages are connected to the device and these are used, the voltage phase rotation is supervised.
On clockwise phase rotation this is done by supervising the phase sequence of the voltages
U
L1
before U
L2
before U
L3
.
This check is done as long as the voltages have a magnitude of at least
|U
L1
|, |U
L2
|, |U
L3
| > 40 V/√3
Wrong phase rotation is indicated by the alarm
Fail Ph. Seq. U
(No 176) .
Setting Notes
Measured Value Monitoring
The sensitivity of the measured value monitoring can be changed. Default values are set at the factory, which
are sufficient in most cases. If especially high operating asymmetry in the currents and/or voltages is to be
expected for the application, or if it becomes apparent during operation that certain monitoring functions acti-
vate sporadically, then the setting should be less sensitive.
The current symmetry supervision can be switched
ON
or
OFF
in address 8101
BALANCE I
, the voltage super-
vision (if available) in address 8102
BALANCE U
.
The current phase sequence can be switched
ON
or
OFF
in address 8105
PHASE ROTAT. I
; the voltage
sequence monitoring (if available) in address 8106
PHASE ROTAT. U
.
In address 8104
SUMMATION U
the voltage sum monitoring
ON
or
OFF
can be set (if available).
Address 8111
BAL. I LIMIT M1
determines the threshold current for measuring location 1 above which
the current balance supervision is effective. Address 8112
BAL. FACT. I M1
is the associated symmetry
factor; that is, the slope of the symmetry characteristic curve. In order to avoid activation during short-term
asymmetries, the monitoring is delayed at address 8113
T Sym. I th. M1
. This parameter can only be set
with DIGSI under Additional Settings. The time delay usually amounts to a few seconds.
The same considerations apply for the further measuring locations, as far as they are available and allocated:
Address 8121
BAL. I LIMIT M2
, 8122
BAL. FACT. I M2
and 8123
T Sym. I th. M2
for measuring
location 2,
Address 8131
BAL. I LIMIT M3
, 8132
BAL. FACT. I M3
and 8133
T Sym. I th. M3
for measuring
location 3,
Address 8141
BAL. I LIMIT M4
, 8142
BAL. FACT. I M4
and 8143
T Sym. I th. M4
for measuring
location 4,
Address 8151
BAL. I LIMIT M5
, 8152
BAL. FACT. I M5
and 8153
T Sym. I th. M5
for measuring
location 5.
Address 8161
BALANCE U-LIMIT
determines the threshold voltage above which the voltage balance super-
vision is effective. Address 8162
BAL. FACTOR U
is the associated symmetry factor, i.e. the slope of the
symmetry characteristic curve (if voltages available). In order to avoid activation during short-term asymme-
tries, the monitoring is delayed at address 8163
T BAL. U LIMIT
. This parameter can only be set with DIGSI
under Additional Settings. The time delay usually amounts to a few seconds.
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
8101
BALANCE I
ON
OFF
OFF
Current Balance Supervi-
sion
8102
BALANCE U
ON
OFF
OFF
Voltage Balance Supervi-
sion
8104
SUMMATION U
ON
OFF
OFF
Voltage Summation Super-
vision
2.19.1.4
2.19.1.5
Functions
2.19 Monitoring Functions
SIPROTEC 4, 7UT6x, Manual
257
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...