No.
Information
Type of
Informa-
tion
Comments
167
Fail U balance
OUT
Failure: Voltage Balance
171
Fail Ph. Seq.
OUT
Failure: Phase Sequence
175
Fail Ph. Seq. I
OUT
Failure: Phase Sequence Current
176
Fail Ph. Seq. U
OUT
Failure: Phase Sequence Voltage
30110
Fail balan. IM1
OUT
Fail.: Current Balance meas. location 1
30111
Fail balan. IM2
OUT
Fail.: Current Balance meas. location 2
30112
Fail balan. IM3
OUT
Fail.: Current Balance meas. location 3
30113
Fail balan. IM4
OUT
Fail.: Current Balance meas. location 4
30114
Fail balan. IM5
OUT
Fail.: Current Balance meas. location 5
30115
FailPh.Seq IM1
OUT
Failure: Phase Sequence I meas. loc. 1
30116
FailPh.Seq IM2
OUT
Failure: Phase Sequence I meas. loc. 2
30117
FailPh.Seq IM3
OUT
Failure: Phase Sequence I meas. loc. 3
30118
FailPh.Seq IM4
OUT
Failure: Phase Sequence I meas. loc. 4
30119
FailPh.Seq IM5
OUT
Failure: Phase Sequence I meas. loc. 5
Trip Circuit Supervision
The differential protection relay 7UT6x is equipped with an integrated trip circuit supervision. Depending on
the number of binary inputs with isolated control inputs that are still available, a choice can be made between
monitoring with one or two binary inputs. If the masking of the required binary inputs does not match the
selected monitoring type, then a message to this effect is generated (
TripC ProgFail
).
Functional Description
Supervision with Two Binary Inputs
If two binary inputs are used, they are connected according to
, one in parallel to the assigned
command relay contact of the protection and the other parallel to the circuit breaker auxiliary contact.
A precondition for the use of the trip circuit supervision is that the control voltage for the circuit breaker is
higher than the total of the minimum voltages drops at the two binary inputs (U
Ctr
> 2 · U
BImin
). Since at least
19 V are needed for each binary input, the supervision function can only be used with a system control
voltage of more than 38 V.
[ausloeselogik-2be-bsp-ausloesekreis1-121102-st, 1, en_GB]
Figure 2-118
Principle of trip circuit supervision using two binary inputs
2.19.2
2.19.2.1
Functions
2.19 Monitoring Functions
SIPROTEC 4, 7UT6x, Manual
259
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...