Test voltage (reg. socket)
500 V; 50 Hz
Transmission speed
100 MBit/s
Bridgeable distance
65.62 feet (20 m)
Ethernet optical (EN100) for DIGSI, IEC61850
Connection for Flush-mounted case rear panel, slot position “B”, duplex LC, 100BaseT acc. to IEEE802.3
Connection for Surface-mounted
case
not available
Transmission Speed
100 MBit/s
Optical wavelength
1300 nm
bridgeable distance
max. 0.93 miles (1.5 km)
1)
limited selection of baud rates for 7UT612
Additional Interface
Connection
isolated interface for data transfer with an RTD-box
Transmission Speed
min. 4,800 Baud; max. 115,200 Baud; Factory setting 38,400 Baud
1)
RS485
Connection for flush-mounted
casing
rear panel, mounting location “D”,
9-pole D-SUB miniature female connector
Connection for surface-mounted
casing
at the housing bottom; shielded data cable
Test Voltage
500 VAC; 50 Hz
Maximum Distance of Transmission 3,280 feet (1,000 m)
Fiber Optical Link (FO)
FO connector type
ST connector
Connection for flush-mounted
casing
Rear panel, mounting location “D”
Connection for surface-mounted
casing
at the housing mounted case on the case bottom
Optical Wavelength
λ = 820 nm
Laser Class 1 according to EN
60825-1/-2
using glass fiber 50/125 μm or using glass fiber 62.5/125 μm
Permissible Optical Link Signal
Attenuation
max. 8 dB, with glass fiber 62.5/125 μm
Maximum Distance of Transmission max. 0.93 miles (1.5 km)
Character Idle State
Configurable: factory setting “Light off”
1)
limited selection of baud rates for 7UT612
Time Synchronization Interface
Time Synchronization
DCF 77 / IRIG B Signal
Connection for flush-mounted case Rear panel, mounting location “A”;
9-pin D-subminiature female connector
Connection for surface mounting
housing
at the double-deck terminal on the case bottom
Signal Nominal Voltages
selectable 5 V, 12 V or 24 V
Test Voltage
500 V; 50 Hz
Technical Data
4.1 General
402
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...